The EE212 humidity (RH) and temperature (T) sensor with interchangeable sensing module is optimized for demanding climate control applications in most various industries.
Versatility
The EE212 is available for wall or duct mount as well as an outdoor version. It features two analogue outputs as well as a BACnet MS/TP or Modbus RTU interface and optional graphic display. Besides the accurate RH and T measurement, the sensor calculates various humidity related parameters such as dew point temperature, absolute humidity and mixing ratio.
Outstanding Reliability
The proprietary coating of the E+E sensing element, the wide choice of filter caps and the IP65 / NEMA 4 enclosure ensure excellent long-term performance of EE212 even under challenging working conditions. Easy on-site replacement of the sensing module minimizes the down-time for maintenance purposes in heavily polluted or aggressive environment.
Interchangeable, Robust Sensing Module
The injection-moulded sensing module inside the sensing head is mechanically highly stable, easy to handle and requires no tools for replacement. The electronics inside the module is encapsulated and therefore best protected against condensation.
User Configurable and Adjustable
The free EE-PCS Product Configuration Software and an optional adapter cable facilitate the configuration and adjustment of the EE212. The configuration includes the measurands assignment (two on the outputs and up to three on the display), the output scale and the display settings.
Appropriate for US mounting requirements
Display
External mounting holes
Electronics on the underside of the PCB
Bayonet Screws
Smooth cover surface
Enclosure
Inspection certificate according DIN EN 10204-3.1
EE212M calibrated sensing module
Measuring range Humdity
0…100% RH
Accuracy Humdity
23 °C ±(1.5+0.005*mv)% RH
-15…60 °C ±(1.8+0.007*mv)% RH
-40…-15 °C additional uncertainty ±0.125 %RH/°C
Measuring range Temperature
-40…60 °C (-40…160 °F)
Accuracy Temperature
±0.3 °C (0.54°F)
Analogue outputs
0-5/10 V or 0/4-20 mA
Digital output
BACnet MS/TP or Modbus RTU